To ensure the normal and safe operation of oil fired boiler,the operating processes must be required strictly because of its particular fuel and the physical properties producing high temperature and pressure.The following sections will introduce some operation specifications of oil fired boiler.

Boiler System

Before making a fire,ensure that no residual oil in furnace,check the nozzle and air register and handle the existing problems.After making a fire,start the induced draft fan and air blower to maintain the pressure in furnace,discharge the combustible gas in furnace to prevent the explosion.After ignition,start the circulating water pump and pay attention to adjust the flame center to ensure its uniform distribution.In the process of making a fire,expert monitoring is needed to handle the flameout timely.After shutdown,prevent the rapid cooling,after fuel cut,stop the air blower first,next,stop the induced draft fan,then,close the smoke duct damper.During the operation,normal detection instrumentation and good maintenance work are also necessary.

Oil Supply System

Oil supply system is the storage area of fuel.Firstly,we should ensure the normal position of valve switch,after starting the oil pump,adjust the overflow valve slowly to ensure the appropriate pressure.Furnace oil temperature should be over 80 degrees,the pressure should be about 588-784 KPA.After shutdown,purge the oil-piping immediately to prevent the condensation of oil deposits.

Water Supply System

Firstly,ensure the quality of water to prevent the slagging and fouling,when the pressure is below 0.3Pa,the softened water should be supplied.

Blower System

According to the combustion conditions,adjust the pressure and air volume reasonably,supply sufficient air to ensure the sufficient burning of fuel and exchange the air blower every four hours.

Zhengzhou Boiler Co., Ltd,the famous industrial boiler manufacturer in central China,always considers the safety as her primary target and receives unanimous favorable comment of customers,so,you will find the appropriate, reliable product here no matter what boiler you want to buy.

Specifications of Oil Fired Boiler,Oil Fired Boiler,Operation Oil Fired Boiler

HOT PRODUCT

HOW TO CONTACT

Chat Online

If you are interested in our products, please feel free to contact us now! Click and chat online.

chatOnline
  • Heat Converters
  • Pressure Converters
  • Temperature Converters

Any question, please contact us for free. Phone number: +86-371-86686767 Skype: zgboiler Email:zbgboiler@zzboiler.com

KW
bar
    °C